Masa
|
●
|
Cables y Accesorios
|
Nominal Diameter |
StandardFlow Range(SFR) |
Extended Flow Range (EFR) |
Standard Pressure Rating |
Customized Pressure Rating | |
(mm) |
(in. ) |
(m 3 /h) |
(m 3 /h) |
(MPa) |
(MPa) - Flange Fitting |
4 |
0.15 |
0.04 to 0.25 |
0.04 to 0.4 |
Thread: 6.3 |
12, 16, 25 |
6 |
0.25 |
0.1 to 0.6 |
0.06 to 0.6 |
Thread: 6.3 |
12, 16, 25 |
10 |
0.4 |
0.2 to 1.2 |
0.15 to 1.5 |
Thread: 6.3 |
12, 16, 25 |
15 |
0.5 |
0.6 to 6 |
0.4 to 8 |
Thread: 6.3; Flange: 2.5 |
4.0, 6.3, 12, 16, 25 |
20 |
0.75 |
0.8 to 8 |
0.45 to 9 |
Thread: 6.3; Flange: 2.5 |
4.0, 6.3, 12, 16, 25 |
25 |
1 |
1 to 10 |
0.5 to 10 |
Thread: 6.3; Flange: 2.5 |
4.0, 6.3, 12, 16, 25 |
32 |
1.25 |
1.5 to 15 |
0.8 to 15 |
Thread: 6.3; Flange: 2.5 |
4.0, 6.3, 12, 16, 25 |
40 |
1.5 |
2 to 20 |
1 to 30 |
Thread: 6.3; Flange: 2.5 |
4.0, 6.3, 12, 16, 25 |
50 |
2 |
4 to 40 |
2 to 40 |
Flange: 2.5 |
4.0, 6.3, 12, 16, 25 |
65 |
2.5 |
7 to 70 |
4 to 70 |
Flange: 2.5 |
4.0, 6.3, 12, 16, 25 |
80 |
3 |
10 to 100 |
5 to 100 |
Flange: 2.5 |
4.0, 6.3, 12, 16, 25 |
100 |
4 |
20 to 200 |
10 to 200 |
Flange: 1.6 |
4.0, 6.3, 12, 16, 25 |
125 |
5 |
25 to 250 |
13 to 250 |
Flange: 1.6 |
2.5, 4.0, 6.3, 12, 16 |
150 |
6 |
30 to 300 |
15 to 300 |
Flange: 1.6 |
2.5, 4.0, 6.3, 12, 16 |
200 |
8 |
80 to 800 |
40 to 800 |
Flange: 1.6 |
2.5, 4.0, 6.3, 12, 16 |
--- |
|
--- |
--- |
--- |
--- |
●
|
Accuracy: 1% preferred, 0.2%, 0.5%
|
●
|
Nominal diameter: DN4-DN300
|
●
|
Working pressure: 1MPa, 1.6MPa, 2.5MPa, 4.0MPa
|
●
|
Medium temperature: -20~+120centigrade(stainless steel) , 0~+120centigrade(PP); -0~+60centigrade(UVPC).
|
●
|
Ambient temperature: -20~+55centigrade
|
●
|
LCD display without output type, 3.6V li battery. (>5 years working time. )
|
●
|
Pulse output type: A, without display pulse output, +5~24VDC
B, LCD display without pulse output, +12~24VDC |
●
|
Two-wire 4-20mA output, +24VDC
|
●
|
Housing protection grade: IP65
|
●
|
Explosion-proof: ExiaIICT4 or ExdIIBT4
|
●
|
Remote: Pulse output signal remote distance ≤ 1000m
|